This fault / information is displayed when the watchdog timer in the PLC detected a disruption of communications with the HMI. Normally this signal will only be displayed for a short time period when a connection is first established by the HMI program. Since the PLC creates this signal it will only be displayed if the problem is intermittent. A complete signal failure will diagnosed by a different fault since the HMI will not receive any signals from the PLC for that case. Possible Causes: 1) System has been initialized after a power up, or restart of the HMI or 2) Ethernet system is experience disruptions on communications. 1) Check Ethernet hardware to insure no cables are damaged. 2) Restart HMI and/or PLC to remove any possible controller internal failure. 3) Check and replace any damaged components - PC (networking card), Ethernet Switch, PLC Ethernet module, etc